٧-٥/٢/٢/٣
ﺘﻭﻓﻴﺭ ﺘﻬﻭﻴﺔ ﻋﻠﻭﻴﺔ ﻤﻌﺘﻤﺩﺓ
.
٧-٥/٣
ﺍﻻﻨﺘﺸﺎﺭ ﺍﻝﺨﺎﺭﺠﻲ
:
ﻴﺠﺏ ﻓﺼل ﻤﺒﺎﻨﻲ ﺃﻭ ﺃﻗﺴﺎﻡ ﺍﻝﺭﻋﺎﻴﺔ ﻋﻥ ﺒﻌﻀﻬﺎ ﺍﻝﺒﻌﺽ ﺒﻭﺍﺴﻁﺔ ﺠﺩﺭﺍﻥ
ﻤﺎﻨﻌﺔ ﻝﻠﺤﺭﻴﻕ ﻤﻘﺎﻭﻤﺘﻬﺎ ﻻ ﺘﻘل ﻋﻥ ﺴﺎﻋﺔ ﻭﺍﺤﺩﺓ
.
٧-٥/٣/١
ﺤﻴﺜﻤﺎ ﺘﺸﺘﺭﻙ ﻤﺒﺎﻨﻲ ﺍﻝﺭﻋﺎﻴﺔ ﻤﻊ ﻨﻭﻉ ﻤﺨﺘﻠﻑ ﻤﻥ ﺍﻝﻤﺒﺎﻨﻲ ﺒﺠﺩﺍﺭ ﻤﺎﻨﻊ ﻝﻠﺤﺭﻴﻕ، ﻴﺠﺏ ﺃﻥ ﻻ
ﺘﻘل ﻤﻘﺎﻭﻤﺔ ﺫﻝﻙ ﺍﻝﺠﺩﺍﺭ ﻋﻥ ﺃﻋﻠﻰ ﺍﻝﻤﺘﻁﻠﺒﺎﺕ ﻷﻱ ﻤﻨﻬﻡ
.
٧-٥/٤
ﻭﺼﻭل ﺁﻝﻴﺎﺕ
ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ
:
ﻴﺠﺏ ﺃﻥ ﻴﺘﻴﺴﺭ ﻭﺼﻭل ﺁﻝﻴﺎﺕ ﻭﻤﻌﺩﺍﺕ ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﻝﻤﺒﺎﻨﻲ
ﺍﻝﺭﻋﺎﻴﺔ
.
٧-٥/٤/١
ﻴﺠﺏ ﺃﻥ ﺘﺘﻤﻜ
ﻥ ﻓﺭﻕ ﺍﻹﻁﻔﺎﺀ ﻤﻥ ﺍﻻﻗﺘﺭﺍﺏ ﻤﻥ ﻤﺒﺎﻨﻲ ﺍﻝﺭﻋﺎﻴﺔ ﺒﺨـﺭﺍﻁﻴﻡ ﻤﻴـﺎﻩ ﺍﻹﻁﻔـﺎﺀ
ﺍﻝﻤﻭﺼﻠﺔ ﺒﻔﻭﻫﺔ ﻤﺂﺨﺫ ﻤﻴﺎﻩ ﺍﻝﺤﺭﻴﻕ ﺃﻭ ﺨﺯﺍﻥ ﺍﻹﻤﺩﺍﺩ ﺒﺎﻝﻤﻴﺎﻩ
.
٧-٥/٤/٢
ﻴﺠﺏ ﺃﻥ ﺘﺘﻤﻜﻥ ﻓﺭﻕ ﺍﻹﻁﻔﺎﺀ ﻤﻥ ﺍﻝﻭﺼﻭل ﺇﻝﻰ ﻓﺘﺤﺎﺕ ﺍﻹﻨﻘﺎﺫ ﺃﻭ ﺍﻝﺸﺭﻓﺎﺕ ﺒﻭﺍﺴﻁﺔ ﺍﻝﺩﺭﺝ ﺃﻭ
ﺃﻴﺔ ﻤﻌﺩﺍﺕ ﺃﺨﺭﻯ ﻝﺘﻨﻔﻴﺫ ﻋﻤﻠﻴﺎﺕ ﺍﻹﻨﻘﺎﺫ
.
٧-٦
ﺴـﺒ
ل ﺍﻝﻬﺭﻭﺏ
)
ﻤﺨﺎﺭﺝ ﺍﻝﻁﻭﺍﺭﺉ
:(
٧-٦/١
ﻴﺠﺏ ﺘﻁﺒﻴﻕ ﺍﻝﺸﺭﻭﻁ ﺍﻝﻌﺎﻤﺔ ﻝﺴـﺒل ﺍﻝﻬﺭﻭﺏ
)
ﻤﺨﺎﺭﺝ ﺍﻝﻁﻭﺍﺭﺉ
(
ﺇﻀﺎﻓﺔ ﻝﻬﺫﻩ ﺍﻝﺸﺭﻭﻁ
.
٧-٦/٢
ﺍﻝﻁﺎﻗﺔ ﺍﻻﺴﺘﻴﻌﺎﺒﻴﺔ
)
ﺍﻻﺴﺘﻴﻌﺎﺏ
:(
ﻴﻘﺩﺭ ﺍﻻﺴﺘﻴﻌﺎﺏ ﻭﻓﻘﺎﹰ ﻝﻤﺎ ﺠﺎﺀ ﻓﻲ ﺒﺎﺏ ﺴــﺒل
ﺍﻝﻬـﺭﻭﺏ
)
ﻤﺨﺎﺭﺝ ﺍﻝﻁﻭﺍﺭﺉ
(
٤-٣ ﺠﺩﻭل
، ﻭﺒﺎﻝﻨﺴﺒﺔ ﻷﻤﺎﻜﻥ ﺍﻻﺴﺘﺨﺩﺍﻤﺎﺕ ﺍﻷﺨﺭﻯ ﻴ
ﺤﺩﺩ ﺍﻻﺴﺘﻴﻌﺎﺏ
ﻝﻜل ﻤﻨﻬﺎ ﻭﻓﻘﺎ ﻝﻁﺒﻴﻌﺔ ﺍﺴﺘﻌﻤﺎﻝﻬﺎ
.
٧-٦/٣
ﺍﻝﺴـﻌـﺔ
:
ﻴﺤﺴﺏ ﻗﻴﺎﺱ ﻋﺭﺽ ﺴﺒل ﺍﻝﻬﺭﻭﺏ ﻋﻠـﻰ ﺃﺴـﺎﺱ ﻋـﺩﺩ ﺍﻷﺸـﺨﺎﺹ ﺍﻝـﺫﻴﻥ
ﻴﺴﺘﺨﺩﻤﻭﻨﻬﺎ ﻜﻤﺎ ﺠﺎﺀ ﻓﻲ ﺒﺎﺏ ﺴـﺒل ﺍﻝﻬﺭﻭﺏ
)
ﻤﺨﺎﺭﺝ ﺍﻝﻁﻭﺍﺭﺉ
ﻋﻠﻰ ﺃﻥ ﻻ ﻴﻘل ﻋﺭﺽ
ﺍﻝﻤﻤﺭﺍﺕ ﺍﻝﺭﺌﻴﺴـﻴﺔ
ﺒﺄﻱ ﺤﺎل
.( ﺴـﻡ ٠٤٢ ) ﻋﻥ
٧-٦/٤
ﻤﺴﺎﻓﺔ ﺍﻻﻨﺘﻘﺎل
:
ﻴﺠﺏ
ﺃﻥ ﻻ ﺘﺯﻴﺩ ﻤﺴﺎﻓﺔ ﺍﻻﻨﺘﻘﺎل ﻤﻥ ﺃﻴﺔ ﻨﻘﻁﺔ ﻝﻠﻭﺼﻭل ﺇﻝﻰ ﺍﻝﻤﺨﺭﺝ ﺍﻝﻨﻬﺎﺌﻲ
ﺃﻭ ﺇﻝﻰ ﺍﻝﺩﺭﺝ ﺍﻝﻤﺤﻤﻲ ﻋﻥ
ﺍﻷﺭﻗﺎﻡ ﺍﻝﻤﺫﻜﻭﺭﺓ ﻓﻲ ﺍﻝﺠﺩﻭل
٧-٢.
:٢-٧ ﺠﺩﻭل
ﺤﺴـﺎﺏ ﻤﺴـﺎﻓﺔ ﺍﻻﻨﺘﻘﺎل ﻭﺍﻝﻤﺴـﺎﻓﺔ ﺍﻝﻤﺒﺎﺸـﺭﺓ ﻝﻤﺒﺎﻨﻲ ﺍﻝﺭﻋﺎﻴﺔ
ﺍﻝﻤﻭﻗﻊ
ﺍﻝﻁﺎﺒﻕ
ﺍﻝﻤﺴﺎﻓﺔ ﺒﺎﻷﻤﺘﺎﺭ
ﺍﻝﺤﺎﻝﺔ ﻭﺍﻝﻤﻼﺤﻅﺎﺕ
ﺍﻝﻤﺴـﺎﻓﺔ ﺍﻝﻤﺒﺎﺸﺭ
ﺓ ﺩﺍﺨل ﻏﺭﻑ
ﺃﻭ
ﺃﺠﻨﺤﺔ ﺍﻝﻨﻭﻡ
ﺍﻷﺭﻀﻲ
١٥
-
ﻤﺴـﺎﻓﺔ ﺍﻻﻨﺘﻘﺎل ﻤﻥ ﺒﺎﺏ ﻏﺭﻑ ﺃﻭ ﺠﻨﺤﺔ
ﺍﻝﻨﻭﻡ ﺇﻝﻰ ﺍﻝﻤﺨﺭﺝ ﺃﻭ ﺍﻝﺩﺭﺝ ﺍﻝﻤﺤﻤﻲ
ﺃﻱ ﻁﺎﺒﻕ
٢٠
ﻝـﻭﺠﻭﺩ ﺃﻜﺜﺭ ﻤﻥ ﻤﺨﺭﺝ ﻭﺍﺤﺩ
ﻭﻝﻭﺠﻭﺩ ﺍﻝﻤﻤﺭﺍﺕ ﺍﻝﺩﺍﺨﻠﻴﺔ
ﺍﻝﻨﻬﺎﻴﺔ ﺍﻝﻤﻐﻠﻘﺔ
ﺃﻱ ﻁﺎﺒﻕ
٧,٥
ﻓﻲ ﺤﺎﻝﺔ ﺍﻝﻨﻬﺎﻴﺔ ﺍﻝﻤﻐﻠﻘﺔ