Prevention and fire protection requirements in the facilities (Part I) second tabah 2008 - page 131

ﺍﻝﺒﺎﺏ ﺍﻝﺴﺎﺩﺱ
١٣٣
٦-٧/٤
ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﻤﻌﺩﺍﺕ ﺍﻝﺤﺭﻴﻕ ﻭﺍﻹﻨﺫﺍﺭ ﻤﻥ ﺤﻴـﺙ ﺍﻝﺘـﺼﻤﻴﻡ ﻭﺍﻝﺘﻨﻔﻴـﺫ ﻭﺍﻝـﺼﻴﺎﻨﺔ ﻭﻓﻘـﺎﹰ
ﻝﻼﺸﺘﺭﺍﻁﺎﺕ ﺍﻝﺨﺎﺼﺔ ﺒﻤﻌﺩﺍﺕ ﺍﻹﻁﻔﺎﺀ ﻭﺍﻹﻨﺫﺍﺭ
ﺃﻭ ﺩﻝﻴل ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ
.
٦-٧/٥
ﻴﺠﻭﺯ ﻝﻠﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﻋﻨﺩ ﺍﻝﺘﺭﺨﻴﺹ، ﺃﻥ ﻴﻁﻠﺏ ﻤﻌ
ﺩﺍﺕ ﺇﻀﺎﻓﻴﺔ ﻜﺒﺩﻴل ﻋﻥ ﺒﻌﺽ ﺍﻻﺤﺘﻴﺎﻁﺎﺕ
ﺍﻝﻭﻗﺎﺌﻴﺔ ﺍﻝﻤﻁﻠﻭﺒﺔ ﻭﻓﻘﺎﹰ ﻝﻠﺸﺭﻭﻁ
.
:٣-٦ ﺠﺩﻭل
ﻤﻌﺩﺍﺕ ﻤﻜﺎﻓﺤﺔ ﺍﻝﺤﺭﻴﻕ ﻝﻤﺒﺎﻨﻲ ﺍﻝﺘﻌﻠﻴﻡ
ﺤﺴﺏ ﺍﻝﻔﺌﺔ ﻭﺍﻻﺭﺘﻔﺎﻉ ﻭﺍﻝﺘﺼﻨﻴﻑ ﺍﻹﻨﺸـﺎﺌﻲ
ﺍﻝﻨﻭﻉ
ﺍﻝﺤﺎﻻﺕ ﺍﻝﻤﻁﻠﻭﺒﺔ
١.
ﻤﻌﺩﺍﺕ ﺍﻹﻁﻔﺎﺀ ﺍﻝﻴﺩﻭﻴﺔ
:
.ﺃ
ﺎﻁﻔ
ﻴﺎﺕ ﻴﺩﻭﻴﺔ
ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ
٢.
ﺍﻝﺘﺭﻜﻴﺒﺎﺕ ﺍﻝﺜﺎﺒﺘﺔ
:
.ﺃ
ﺸﺒﻜﺔ ﺨﺭﺍ
ﻁﻴﻡ ﻤﻁﺎﻁﻴﺔ
ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ
.ﺏ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺠﺎﻓﺔ
ﺃﻜﺜﺭ ﻤﻥ
ﺃﺭﻀﻲ ) ﻁﻭﺍﺒﻕ ٤
+
ﺜﻼﺜﺔ ﻁﻭﺍﺒﻕ
(
ﻭﺒﺎﺭﺘﻔﺎﻉ ﺃﻗل ﻤـﻥ
٢٨
ﻤﺘﺭ ﺃﻭ ﻁﺎﺒﻘﻴﻥ ﺒﻤﺴﺎﺤﺔ ﺇﺠﻤﺎﻝﻴﺔ ﺘﺯﻴﺩ ﻋﻥ
ﻡ ٠٠٠١
٢
.
.ﺝ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺭﻁﺒﺔ
ﺎﺒ
ﺭﺘﻔﺎﻉ ﺃﻋﻠﻰ ﻤﻥ
٢٨
ﻤﺘﺭ ﺃﻭ ﺃﻜﺜﺭ ﻤﻥ ﻁﺎﺒﻘﻴﻥ ﺒﻤﺴﺎﺤﺔ ﺘﺯﻴـﺩ ﻋـﻥ
ﻡ ٠٠٠١
٢
ﻝﻠﻁﺎﺒﻕ ﺍﻝﻭﺍﺤﺩ
.
.ﺩ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺨﺎﺭﺠ
ﻴﺔ
ﻓﻲ
ﺴـﺎﺤﺎﺕ ﺍﻝﺠﺎﻤﻌﺎﺕ ﻭﺍﻝﻤﻌﺎﻫﺩ ﺍﻝﻌﻠﻴﺎ
.
٣.
ﺍﻷﻨﻅﻤﺔ ﺍﻝﺘﻠﻘﺎﺌﻴﺔ ﺍﻝﺜﺎﺒﺘﺔ
:
.ﺃ
ﺸﺒﻜﺔ ﺘﻠﻘﺎﺌﻴﺔ ﻝﻤﺭﺸﺎﺕ ﻤﻴﺎﻩ
ﻤﻜﺎﻓﺤﺔ ﺍﻝﺤﺭﻴﻕ
ﺍﻝﺴﺭﺩﺍﺏ، ﺍﻷﺩﻭﺍﺭ ﺍﻝﻌﻠﻴﺎ ﺍﻝﺘﻲ ﺘﺯﻴﺩ ﻋﻥ
٤
ﺃﺩﻭﺍﺭ، ﺍﻝﻤﺒﺎﻨﻲ ﺍﻝﻤﻨﺸﺄﺓ ﻤﻥ
ﺍﻝﻨﻭﻉ ﺍﻝﺜﺎﻝﺙ ﻭﺍﻝﺨﺎﻤﺱ
.
.ﺏ
ﺸﺒﻜﺔ ﺘﻠﻘﺎﺌﻴﺔ ﻝﻤﺭﺸﺎﺕ ﻤﻭﺍﺩ
ﺃﺨﺭﻯ
ﺃﻤﺎﻜﻥ ﺍﻝﺨﻁﻭﺭﺓ ﺍﻝﺨﺎﺼﺔ ﺤﻴﺙ ﻻ ﻴﻤﻜ
ﻥ ﺍﺴﺘﺨﺩﻡ ﺍﻝﻤﻴﺎﻩ
.
٤.
ﻤﻌﺩﺍﺕ ﺇﻨﺫﺍﺭ ﺍﻝﺤﺭﻴﻕ
:
.ﺃ
ﺸﺒﻜﺔ ﺇﻨﺫﺍﺭ ﻴﺩﻭﻱ
ﻓﻲ ﺍﻝﺼﺎﻻﺕ ﻤﺘﻌﺩﺩﺓ ﺍﻷﻏﺭﺍﺽ، ﻭﻤﻤﺭﺍﺕ ﺍﻹﺩﺍﺭﺓ، ﻭﻤﻤﺭﺍﺕ ﺍﻝﻔﺼﻭل
ﺍﻝﻤﻐﻠﻘﺔ ﻓﻲ ﺠﻤﻴﻊ ﺍﻝﻤﺭﺍﺤل ﺒﺎﺴﺘﺜﻨﺎﺀ ﻤﻤﺭﺍﺕ ﺍﻝﻔﺼﻭل ﺍﻝﻤﻜﺸﻭﻓﺔ
.
.ﺏ
ﺸﺒﻜﺔ ﺇﻨﺫﺍﺭ ﺘﻠﻘﺎﺌﻲ
ﻓﻲ ﺍﻝﻭﺭﺵ
، ﻭﺍﻝﻤﺨﺘﺒﺭﺍﺕ، ﻭﺍﻝﻤﺨﺎﺯﻥ
، ﻭﺍﻝﻤﻜﺘﺒﺔ
، ﻭ ﻓـﻲ ﺍﻝـﺼﺎﻻ
ﻤﺘﻌﺩﺩﺓ ﺍﻷﻏﺭﺍﺽ
ﻤﻊ ﺇﻨﺫﺍﺭ ﻴﺩﻭﻱ
،
ﻭﻜﺫﻝﻙ ﻓـﻲ ﺃﻤـﺎﻜﻥ ﺍﻝﺨﻁـﻭﺭﺓ
ﺍﻝﺨﺎﺼﺔ
، ﻭﻤﺠﺎﺭﻱ ﺍﻝﺘﻜﻴﻴﻑ
، ﻭﺍﻝﺴﺭﺩﺍﺏ
.
1...,132,133,134,135,136,137,138,139,140,141 121,122,123,124,125,126,127,128,129,130,...207
Powered by FlippingBook