Prevention and fire protection requirements in the facilities (Part I) second tabah 2008 - page 121

ﺍﻝﺒﺎﺏ ﺍﻝﺨﺎﻤﺱ
١٢٣
ﺠﺩﻭل ﺭﻗﻡ
٥-٢:
ﻤﻌﺩﺍﺕ ﻤﻜﺎﻓﺤﺔ ﺍﻝﺤﺭﻴﻕ ﻝﻤﺒﺎﻨﻲ ﺍﻝﺘﺠﻤﻌﺎﺕ
ﺤﺴﺏ ﺍﻝﻔﺌﺔ ﻭﺍﻻﺭﺘﻔﺎﻉ ﻭﺍﻝﺘﺼﻨﻴﻑ ﺍﻹﻨﺸـﺎﺌﻲ
ﺍﻝﻨﻭﻉ
ﺍﻝﺤﺎﻻﺕ ﺍﻝ
ﻤﻁﻠﻭﺒﺔ
١.
ﻤﻌﺩﺍﺕ ﺍﻹﻁﻔﺎﺀ ﺍﻝﻴﺩﻭﻴﺔ
:
.ﺃ
ﺎﻁﻔ
ﻴﺎﺕ ﻴﺩﻭﻴﺔ
ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ
٢.
ﺍﻝﺘﺭﻜﻴﺒﺎﺕ ﺍﻝﺜﺎﺒﺘﺔ
:
.ﺃ
ﺸﺒﻜﺔ ﺨﺭﺍﻁﻴﻡ ﻤﻁﺎﻁﻴﺔ
ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ
.ﺏ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺠﺎﻓﺔ
ﺃﻜﺜﺭ ﻤﻥ
ﺃﺭﺒﻌﺔ ﻁﻭﺍﺒﻕ
ﺃﺭﻀﻲ )
+
( ﻁﻭﺍﺒﻕ ﺔ ﺜﻼﺜ
ﻭﺒﺎﺭﺘﻔﺎﻉ ﺃﻗل ﻤـﻥ
٢٨
ﻤﺘﺭ ﺃﻭ ﻁﺎﺒﻘﻴﻥ ﺒﻤﺴﺎﺤﺔ ﺇﺠﻤﺎﻝﻴﺔ ﺘﺯﻴﺩ ﻋﻥ
ﻡ ٠٠٠١
٢
.
.ﺝ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺭﻁﺒﺔ
ﺒﺎﺭﺘ
ﻔﺎﻉ ﺃﻋﻠﻰ ﻤﻥ
٢٨
ﻤﺘﺭ ﺃﻭ ﺃﻜﺜﺭ ﻤﻥ ﻁﺎﺒﻘﻴﻥ ﺒﻤﺴﺎﺤﺔ ﺘﺯﻴـﺩ ﻋـﻥ
ﻡ ٠٠٠١
٢
ﻝﻠﻁﺎﺒﻕ ﺍﻝﻭﺍﺤﺩ
.
.ﺩ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺨﺎﺭﺠﻴﺔ
ﺤﺴﺏ ﺤﺠﻡ ﺍﻝﻤﺒﻨﻰ
٣.
ﺍﻷﻨﻅﻤﺔ ﺍﻝﺘﻠﻘﺎﺌﻴﺔ ﺍﻝﺜﺎﺒﺘﺔ
:
.ﺃ
ﺸﺒﻜﺔ ﺘﻠﻘﺎﺌﻴﺔ ﻝﻤﺭﺸﺎﺕ ﻤﻴﺎﻩ
ﻤﻜﺎﻓﺤﺔ ﺍﻝﺤﺭﻴﻕ
ﺤﺴﺏ ﺍﻝﺠﺩﻭل ﺭﻗﻡ
٥-٣"
ﻤﺘﻁﻠﺒﺎﺕ ﻤﺭﺸﺎﺕ ﻤﻴﺎﻩ ﻤﻜﺎﻓﺤـﺔ ﺍﻝﺤﺭﻴـﻕ
ﻝﻤﺒﺎﻨﻲ ﺍﻝﺘﺠﻤﻌﺎﺕ
".
.ﺏ
ﺸﺒﻜﺔ
ﺘﻠﻘﺎﺌﻴﺔ ﻝﻤﺭﺸﺎﺕ ﻤﻭﺍﺩ
ﺃﺨﺭﻯ
ﺃﻤﺎﻜﻥ ﺍﻝﺨﻁﻭﺭﺓ ﺍﻝﺨﺎﺼﺔ ﺤﻴﺙ ﻻ ﻴﻤﻜﻥ ﺍﺴﺘﺨﺩﻡ ﺍﻝﻤﻴﺎﻩ
٤.
ﻤﻌﺩﺍﺕ ﺇﻨﺫﺍﺭ ﺍﻝﺤﺭﻴﻕ
:
.ﺃ
ﺸﺒﻜﺔ ﺇﻨﺫﺍﺭ ﻴﺩﻭﻱ
ﻓﻲ ﺍﻝﺼﺎﻻﺕ ﻤﺘﻌﺩﺩﺓ ﺍﻷﻏﺭﺍﺽ ، ﻭﺍﻝﻤﻤﺭﺍﺕ
.
.ﺏ
ﺸﺒﻜﺔ ﺇﻨﺫﺍﺭ ﺘﻠﻘﺎﺌﻲ
ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ