Prevention and fire protection requirements in the facilities (Part I) second tabah 2008 - page 114

ﺍﻝﺒﺎﺏ ﺍﻝﺭﺍﺒﻊ
١١٦
٤-١٢/١٠/٤
ﻤﺘﻁﻠﺒﺎﺕ ﺍﻝﻭﻗﺎﻴﺔ ﻓﻲ ﺘﻭﺼﻴل ﺍﻝﻤﻭﺍﻗﺩ ﺒﺄﻨﺎﺒﻴﺏ ﺘﻭﺼﻴل ﺍﻝﻐﺎﺯ ﺍﻝﺒﺘﺭﻭﻝﻲ ﺍﻝﻤﺴﺎل
:
٤-١٢/١٠/٤/١
ﻴﺘﻡ ﺘﻭﺼﻴل ﺍﻝﻤﻭﺍﻗﺩ ﺒﺄﻨﺎﺒﻴﺏ ﻤﻥ ﻨﺤﺎﺱ ﺃﻭ ﺤﺩﻴﺩ ﻤﻊ ﻭﻀﻊ ﺼﺎﻤﻭﻝﺔ ﻝﺘﺴﻬﻴل ﻋﻤﻠﻴﺔ
ﺍﻝﻔﻙ ﻭﺍﻝﺭﺒﻁ ﻓﻲ ﺍﻝﻤﺴﺘﻘﺒل
.
٤-١٢/١٠/٤/٢
ﻴﺴﻤﺢ ﺒﺎﺴﺘﻌﻤﺎل ﺍﻝﺨﺭﺍﻁﻴﻡ ﺍﻝﻤﻁﺎﻁﻴﺔ ﺒﻌﺩ ﺍﻝﻤﻨﻅﻡ ﺍﻝﺜ
ﺎﻨﻲ ﻝﻠﻀﻐﻁ ﺍﻝﻤﻨﺨﻔﺽ ﺒـﺸﺭﻁ
ﺃﻥ ﻻ ﻴﺯﻴﺩ ﻁﻭل ﺍﻝﺨﺭﻁﻭﻡ ﻋﻥ ﺴـﺘﺔ ﺃﻗﺩﺍﻡ
(. ﺴـﻡ ٠٨١ )
٤-١٢/١٠/٤/٣
ﻴﺠﺏ ﺃﻥ ﻴﻭﻀﻊ ﺼﻤﺎﻡ ﻝﻜل ﺠﻬﺎﺯ ﻏﺎﺯ ﻭﻴﻜﻭﻥ ﻗﺭﻴﺒﺎ ﻤﻨﻪ ﺤﺘﻰ ﻴﺘﻴﺴﺭ ﻋﺯﻝﻪ ﻭﻓﺼﻠﻪ
ﺩﻭﻥ ﺃﻥ ﻴﻘﻁﻊ ﺍﻝﻐﺎﺯ ﻋﻠﻰ ﺍﻷﺠﻬﺯﺓ ﺍﻷﺨﺭﻯ
.
ﻭﻴﺨﻀﻊ ﻫﺫﺍ ﺍﻝـﺼﻤﺎﻡ ﻝﻠﻤﻭﺍﺼـﻔﺎﺕ
ﺍﻝﻤﻌﺘﺭﻑ ﺒﻬﺎ ﺤﺘﻰ ﻴﻜﻭﻥ ﺼﺎﻝﺤﺎ ﻝﻼﺴﺘﻌﻤﺎل
ﻓﻲ ﺨﻁﻭﻁ ﺍﻝﻐﺎﺯ ﺍﻝﻤﺴﺎل
.
٤-١٢/١١
ﺍﺤﺘﻴﺎﻁﺎﺕ ﻭﻗﺎ
ﻴﺔ ﻋﺎﻤﺔ ﻝﻠﺤﻤﺎﻴﺔ ﻤﻥ ﺍﻝﺤﺭﻴﻕ ﻝﻨﻅﺎﻡ ﺍﻝﻐﺎﺯ ﺍﻝﺒﺘﺭﻭﻝﻲ ﺍﻝﻤﺴﺎل ﺍﻝﻤﺭﻜﺯﻱ
:
٤-١٢/١١/١
ﻴﺠﺏ ﺇﺸﻌﺎﺭ ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﺒﻭﺴﺎﺌل ﺍﻻﺤﺘﻴﺎﻁ ﻀﺩ ﺍﻝﺤﺭﻴﻕ ﻓﻲ ﻤﺭﺤﻠﺔ ﺘﺼﻤﻴﻡ ﺍﻝﻤﺸﺭﻭﻉ
ﻭﻓﻲ ﻤﺭﺍﺤل ﺍﻝﺘﻨﻔﻴﺫ ﻭ
ﻗﺒل
ﺍﻝﺘﺸﻐﻴل
.
٤-١٢/١١/٢
ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﻜل ﺘ
ﻤﺩﻴﺩﺍﺕ ﺠﻬﺎﺯ ﺍﻝﻐﺎﺯ ﺍﻝﻤﺭﻜﺯﻱ ﻤﺠﺭﺒﺔ ﺒﺎﻝﻀﻐﻁ ﺍﻝﻤﻨﺎﺴﺏ ﺤﺘﻰ ﻴﺘﻡ
ﺍﻝﺘﺄﻜﺩ ﻋﻠﻰ ﺃﻨﻬﺎ ﺒﻜﺎﻤل ﺍﻝﺩﻗﺔ ﻭﺨﺎﻝﻴﺔ ﻤﻥ ﺍﻝﻌﻴﻭﺏ ﻭﺍﻝﻨﻭﺍﻗﺹ ﻭﺫﻝﻙ ﻗﺒل ﺘﺸﻐﻴﻠﻬﺎ ﺒﺎﻝﻐﺎﺯ
.
٤-١٢/١١/٣
ﺘﻭﻓﻴﺭ ﻨﻅﻡ ﺍﻹﻨﺫﺍﺭ ﻭﺍﻹﻁﻔﺎﺀ
ﺍﻝﻤﻼﺌﻤﺔ
ﻝﻐﺎﺯ ﺍﻝﺒﺘﺭﻭل ﺍﻝﻤﺴﺎل
،
ﻭﻭﻀـﻌﻬﺎ ﻓـﻲ ﺃﻤـﺎﻜﻥ
ﺘ ﺇﺴ
ﺭﺍﺘﻴﺠﻴﺔ
ـ ﻭﻗﺭﻴﺒ
ﺔ ﻤﻥ ﻤﺤﻁﺔ ﺍﻝﻐﺎﺯ
.
٤-١٢/١١/٤
ﻭﻀﻊ ﻻﻓﺘﺎﺕ ﺘﺤﺫﻴﺭﻴﺔ ﻤﻥ ﺃﺠل ﺍﻝﺴﻼﻤﺔ ﻓﻲ ﺍﻝﻤﻨﻁﻘﺔ ﺤﻭل ﺍﻝﺨﺯﺍﻥ ﻤﺜـل
/
ﻤﻤﻨـﻭﻉ
ﺍﻝﺘﺩﺨﻴﻥ
،
ﻭﻋﺒﺎﺭﺍﺕ ﺘﻔﻴﺩ ﻭﺠﻭﺩ ﺨﺯﺍﻥ ﻝﻠﻐﺎﺯ
،
ﻭﻤﻨﺎﻁﻕ ﻻ ﺘﺤﺘﻤل ﻭﺠﻭﺩ ﻤـﻭﺍﺩ ﻤﻠﺘﻬﺒـﺔ
.ﻪـ ﻭﺨﻼﻓ
٤-١٢/١١/٥
ﻴﺠﺏ ﺃﻥ ﺘﺠﻬﺯ ﺍﻝﻤﻁﺎﺒﺦ ﺍﻝﺩﺍﺨﻠﻴﺔ ﺒﺄﺠﻬﺯﺓ ﺇﻨﺫﺍﺭ ﺘﺴﺭﺏ ﺍﻝﻐﺎﺯ
،
ﻭﻫﺫﻩ ﺍﻷﺠﻬﺯﺓ ﺘﻘﻁﻊ ﻤﺩ
ﺍﻝﻐﺎﺯ ﺘﻠ
ﻘﺎﺌﻴﺎ ﻓﻲ ﺤﺎﻝﺔ ﺘﺴﺭﺏ ﺍﻝﻐﺎﺯ
.
1...,115,116,117,118,119,120,121,122,123,124 104,105,106,107,108,109,110,111,112,113,...207