Prevention and fire protection requirements in the facilities (Part I) second tabah 2008 - page 28

ﺍﻝﺒﺎﺏ
ﺍﻷﻭل
٣٠
١-٧/٧
ﺍﻻﻨﺘﺸـﺎﺭ ﺍﻝﺨﺎﺭﺠﻲ ﺒﻴﻥ ﻗﻁﺎﻋﺎﺕ ﺍﻝﺤﺭﻴﻕ
:
ﻻﺴـﺘﻜﻤﺎل ﻋﻤﻠﻴﺔ ﺍﻝﺴـﻴﻁﺭﺓ ﻋﻠﻰ ﺍﻨﺘﺸـﺎﺭ ﺍﻝﺤﺭﻴﻕ ﺩﺍﺨل ﺍﻝﻤﺒﻨﻰ ﻴﺠﺏ ﺘﻭﻓﺭ ﺍﻝـﺸـﺭﻭﻁ
ﺍﻝﺘﻲ ﺘﻤﻨﻊ ﺍﻻﻨﺘﺸـﺎﺭ ﺒﻴﻥ ﻗﻁﺎﻋﺎﺕ ﺍﻝﺤﺭﻴﻕ ﻤﻥ ﺨﻼل ﺍﻝﻔﺘﺤﺎﺕ ﺍﻝﻤﻁﻠـﺔ ﻋﻠـﻰ ﺍﻝﻭﺍﺠﻬـﺎﺕ
ﺍﻝﺨﺎﺭﺠﻴﺔ ﺃﻭ ﺍﻝﺴـﻁﺢ ﺃﻭ ﺍﻝﻤﻨﺎﻭﺭ ﻭﻓﻘﺎ ﻝﻤﺎ ﻴﻠﻲ
:
١-٧/٧/١
ﺍﻝﻨﻭ
ﺍﻓﺫ ﻋﻠﻰ ﺍﻝﻭﺍﺠﻬﺎﺕ ﺍﻝﺨﺎﺭﺠﻴﺔ ﻴﺠﺏ ﺃﻥ ﻻ ﺘﻘل ﺍﻝﻤﺴﺎﻓﺔ ﺒﻴﻥ ﻨﺎﻓﺫﺘﻴﻥ ﻤﺘﺠﺎﻭﺭﺘﻴﻥ ﻝﻘﻁﺎﻋﻲ
ﺤﺭﻴﻕ ﻤﺨﺘﻠﻔﻴﻥ ﻭﻓﻲ ﻨﻔﺱ ﺍﻝﻤﺴﺘﻭﻯ ﻋﻥ ﺍﻝﺤﺩ ﺍﻝﺘﺎﻝﻲ
:
١-٧/٧/١/١
ﻡ ٠٥,٠
ﺇﺫﺍ ﻜﺎﻨﺘﺎ ﻋﻠﻰ ﻭﺍﺠﻬﺔ ﻤﺴـﺘﻭﻴﺔ
.
١-٧/٧/١/٢
ﻡ ٠٢,١
ﺇﺫﺍ ﻜﺎﻨﺘﺎ ﻋﻠﻰ ﻭﺍﺠﻬﺘﻴﻥ ﻋﻠﻲ ﺸﻜل ﺯﺍﻭﻴﺔ
.
١-٧/٧/١/٣
ﻡ ٠٠,٣
ﻓﻲ ﺤﺎﻝﺔ
ﻨﺎﻓﺫﺓ ﺍﻝﺩﺭﺝ ﺍﻝﻤﺠﺎﻭﺭﺓ ﻝﻨﺎﻓﺫﺓ ﻗﻁﺎﻉ ﺤﺭﻴﻕ ﺁﺨﺭ
.
ﺍﻝﺸﻜل
١-٦:
ﻤﻨﻊ ﺍﻨﺘﻘﺎل ﺍﻝﺤﺭﻴﻕ ﻤﻥ ﺨﻼل ﻨﺎﻓﺫﺘﻴﻥ ﻤﺘﺠﺎﻭﺭﺘﻴﻥ ﻋﻠﻰ ﺸﻜل ﺨﻁ ﻤﺴﺘﻘﻴﻡ
ﺍﻝﺸﻜل
١-٧:
ﻤﻨﻊ ﺍﻨﺘﻘﺎل ﺍﻝﺤﺭﻴﻕ ﻤﻥ ﺨﻼل ﻨﺎﻓﺫﺘﻴﻥ ﻤﺘﺠﺎﻭﺭﺘﻴﻥ ﻋﻠﻰ ﺸﻜل ﺯﺍﻭﻴﺔ
ﺍﻝﺸﻜل
١-٨:
ﻤﻨﻊ ﺍﻨﺘﻘﺎل ﺍﻝﺤﺭﻴﻕ ﺭﺍﺴﻴﺎ ﻤﻥ ﺨﻼل ﺍﻝﻭﺍﺠﻬﺔ