Prevention and fire protection requirements in the facilities (Part I) second tabah 2008 - page 34

ﺍﻝﺒﺎﺏ
ﺍﻷﻭل
٣٦
١-٨/٩
ﺍﻷﺴﻘﻑ
ﺍﻝﻤﻌﻠﻘﺔ
)
ﺍﻝﻤﺴﺘﻌﺎﺭﺓ
: (
١-٨/٩/١
ﺘﻨﺸﺄ ﺍﻷﺴﻘﻑ
)
ﺍﻷﻝﻭﺍﺡ ، ﻭﺍﻝﻬﻴﻜل
(
ﻤﻥ ﻤﺎﺩﺓ ﻏﻴﺭ ﻗﺎﺒﻠﺔ ﻝﻼﺸﺘﻌﺎل
.
١-٨/٩/٢
ﻴﺠﻭﺯ ﺃﻥ ﺘﻨﺸﺄ ﺍﻷﺴﻘﻑ ﺍﻝﻤﻌﻠﻘﺔ ﻤﻥ ﻤﺎﺩﺓ ﻗﺎﺒﻠﺔ ﻝﻼﺤﺘﺭﺍﻕ ﻓﻲ ﺤﺎﻻﺕ ﻤﻌﻴﻨﺔ ﻴﻌﻭﺩ ﺘﻘﺩﻴﺭﻫﺎ
ﻝﻠﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﻭﺒﻤﺭﺍﻋﺎﺓ ﺍﻝﺸﺭﻭﻁ ﺍﻝﺘﺎﻝﻴﺔ
:
١-٨/٩/٢/١
ﺃﻻ ﺘﻜﻭﻥ ﻓﻲ ﻤﻜﺎﻥ ﻴﺤﺘﻤل ﻓﻴﻪ ﻨﺸﻭﺏ ﺍﻝﺤﺭﻴﻕ ﺃﻭ ﻴﺘﻭﺍ
ﺠﺩ ﻓﻴﻪ ﺍﻝﺠﻤﻬﻭﺭ ﺃﻭ ﻴﺸﻜل
ﺠﺯﺀﺍﹰ ﻤﻥ ﻤﺴﻠﻙ ﺍﻝﻬﺭﻭﺏ
.
١-٨/٩/٢/٢
ﺃﻻ ﺘﺯﻴﺩ ﺍﻝﻤﺴﺎﺤﺔ ﺍﻝﻜﻠﻴﺔ ﻋﻥ ﺜﻤﺎﻨﻴﺔ ﻭﻋﺸﺭﻭﻥ ﻤﺘﺭﺍﹰ ﻤﺭﺒﻌﺎﹰ
.
١-٨/٩/٢/٣
ﺃﻥ ﻴﻔﺼل ﺍﻝﺴﻘﻑ ﻋﻤﺎ ﻴﺠﺎﻭﺭﻩ ﻤﻥ ﺍﻷﺴﻘﻑ ﺒﺭﻓﻊ ﺍﻝﺠﺩﺭﺍﻥ ﺍﻝﻤﺤﻴﻁﺔ ﺒﻪ ﺇﻝﻰ ﺍﻝﺴﻘﻑ
ﺍﻷﺼﻠﻲ
.
١-٨/٩/٢/٤
ﺃﻻ ﻴﺘﻌﺎﺭﺽ ﺃﺴﻠﻭﺏ ﺇﻨﺸﺎﺌﻬﺎ
ﻤﻊ ﺍﻝﺸﺭﻭﻁ ﺍﻝﻭﻗﺎﺌﻴﺔ
ﺍﻝﺘﻁﺒﻴﻘﻴﺔ ﻻ
ﺍﻝﺒﻨﺎﺀ ل ﺴﺘﻌﻤﺎ
.
١-٨/١٠
ﺍﻝﺘﻐﻠﻴﻑ ﺍﻝﺨﺎﺹ ﺒﺎﻝﻌﺯل ﺍﻝﺤﺭﺍﺭﻱ ﺃﻭ ﺍﻝﺼﻭﺘﻲ ﺃﻭ ﺍﻝﺘﻐﻠﻴﻑ ﺍﻝﺯﺨﺭﻓﻲ
)
ﺍﻝﺩﻴﻜﻭﺭ
: (
١-٨/١٠/١
ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺍﻝﻤﻭﺍﺩ ﺍﻝﻤﺴﺘﺨﺩﻤﺔ ﻷﻏﺭﺍﺽ ﺍﻝﺯﺨﺭﻓﺔ ﻭﺍﻝﺘﺠﻤﻴل
)
ﺍﻝﺩﻴﻜﻭﺭ
(
ﺃﻭ ﺍﻝﻌﺯل ﺍﻝﺤﺭﺍﺭﻱ
ﺃﻭ ﺍﻝﺼﻭﺘﻲ ، ﻤﻘﺎﻭﻤﺔ ﻝﻠﺤﺭﻴﻕ ﻭﺫﺍﺕ ﺩﺭﺠﺔ ﻻﻨﺘﺸﺎﺭ ﺍﻝﻠﻬﺏ ﻻ ﺘﻘل ﻋ
. ﻥ ﺼﻔﺭ
١-٨/١٠/٢
ﻓﻲ ﺤﺎﻝﺔ ﺍﺴﺘﺨﺩﺍﻡ ﻤﻭﺍﺩ ﻗﺎﺒﻠﺔ ﻝﻼﺤﺘﺭﺍﻕ ﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﻤﻌﺎﻝﺠﺔ ﻫﺫﻩ ﺍﻝﻤﻭﺍﺩ ﻜﻴﻤﻴﺎﺌﻴﺎﹰ ﺃﻭ ﺘﻐﻠﻴﻔﻬﺎ
ﺒﻁﻼﺀ ﻤ
ﺨﺭ ﻝﻼﺸ ﺅ
ﺘﻌﺎل ﺒﺤﻴﺙ ﺘﻜﻭﻥ ﺴﻁﺤﺎﹰ ﻤﻘﺎﻭﻤﺎﹰ ﻻ
ﻨﺘﺸﺎﺭ ﺍﻝﻠﻬﺏ ﻝﻤﺩﺓ ﻻ ﺘﻘل ﻋﻥ ﺴﺎﻋﺔ
.
١-٨/١٠/٣
ﻴﺠﻭﺯ ﺍﺴﺘﻌﻤﺎل ﺍﻝﺨﺸﺏ ﻓﻲ ﺘﺒﻠﻴﻁ ﺍﻷﺭﻀﻴﺎﺕ
)
ﺒﺎﺭﻜﻴﻪ
(
ﻓﻲ ﺤﺎﻻﺕ ﻤﻌﻴﻨﺔ ﻴ
ﻌﻭﺩ ﺘﻘﺩﻴﺭﻫﺎ ﻝﻠﺩﻓﺎﻉ
ﺍﻝﻤﺩﻨﻲ ﻭﺒﻤﺭﺍﻋﺎﺓ ﺍﻝﺸﺭﻭﻁ ﺍﻝﺘﺎﻝﻴﺔ
:
١-٨/١٠/٣/١
ﺃﻥ ﻴﻜﻭﻥ ﺍﻝﺨﺸﺏ ﻤﻥ ﺍﻝﻨﻭﻉ ﺍﻝﻘﺎﺴﻲ
.
١-٨/١٠/٣/٢
ﺃﻥ ﻴﺴﺘﻌﻤل ﻓﻲ ﻤﻜﺎﻥ ﻻ ﺨﻁﻭﺭﺓ ﻝﻨﺸﻭﺏ ﺤﺭﻴﻕ ﻓﻴﻪ ﻭﻻ ﻴﺘﻭﺍﺠﺩ ﻓﻴﻪ ﺍﻝﺠﻤﻬﻭﺭ
ﻭﻴﻭﺍﻓﻕ ﻋﻠﻴﻪ ﻤﻥ ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ
.
١-٨/١٠/٣/٣
ﻴﺠﻭﺯ ﺍﺴﺘﻌﻤﺎل ﺍﻝﻤﻭﺍﺩ ﺍﻝﻘﺎﺒﻠﺔ ﻝﻼﺤﺘﺭﺍﻕ ﻝﺘ
ﻐﻠﻴﻑ ﺍﻝﺠﺩﺭﺍﻥ ﻓﻲ ﺤﺎﻻﺕ ﻤﻌﻴﻨﺔ ﻴﻌﻭﺩ
ﺘﻘﺩﻴﺭﻫﺎ ﻝﻠﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﻭﺒﻤﺭﺍﻋﺎﺓ ﺍﻝﺸﺭﻭﻁ ﺍﻝﺘﺎﻝﻴﺔ
:
.ﺃ
ﺃﻥ ﻻ ﺘﻜﻭﻥ ﻓﻲ ﻤﻜﺎﻥ ﻴﺤﺘﻤل ﻓﻴﻪ ﻨﺸﻭﺏ ﺍﻝﺤﺭﻴﻕ ﺃﻭ ﻴﺘﻭﺍﺠﺩ ﻓﻴﻪ ﺍﻝﺠﻤﻬﻭﺭ ﺃﻭ
ﻴﺸﻜل ﺠﺯﺀﺍﹰ ﻤﻥ ﻤﺴﻠﻙ ﺍﻝﻬﺭﻭﺏ
.
.ﺏ
ﺃﻥ ﺘﻜﻭﻥ ﺍﻝﻤﻭﺍﺩ ﺍﻝﻤﺴﺘﺨﺩﻤﺔ ﻤﻘﺎﻭﻤﺔ ﻝﻠﺤﺭﻴﻕ ﻭﺫﺍﺕ ﺩﺭﺠﺔ ﻻﻨﺘﺸﺎﺭ ﺍﻝﻠﻬﺏ ﻻ ﺘﻘل
ﻋﻥ ﺼﻔﺭ
ﻭﻓﻲ ﺤﺎﻝﺔ ﺍﺴﺘﺨﺩﺍﻡ ﻤﻭﺍﺩ ﻗﺎﺒﻠﺔ ﻝﻼﺤﺘﺭﺍﻕ ﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﻤﻌﺎﻝﺠﺔ ﻫﺫﻩ
ﺍﻝﻤﻭﺍﺩ ﻜﻴﻤﻴﺎﺌﻴﺎﹰ ﺃﻭ ﺘﻐﻠﻴﻔﻬﺎ ﺒﻁﻼﺀ ﻤ
ﺨﺭ ﻝﻼﺸﺘﻌﺎل ﺒﺤﻴﺙ ﺘﻜﻭﻥ ﺴﻁﺤﺎﹰ ﻤﻘﺎﻭﻤﺎﹰ
ﻻﻨﺘﺸﺎﺭ ﺍﻝﻠﻬﺏ ﻝﻤﺩﺓ ﻻ ﺘﻘل ﻋﻥ ﺴﺎﻋﺔ ﻋﻠﻰ ﺃﻥ ﺘﻜﻭﻥ ﻓﻭﻕ ﻤﺴﺘﻭﻯ ﺍﻷﺭﻀﻴﺔ
ﺒﻤﻘﺩﺍﺭ
٧٦
ﺴﻡ ، ﻭﺃﻥ ﺘﻜﻭﻥ ﻤﺜﺒﺘﺔ ﻋﻠﻰ ﺴﻁﺢ ﺍﻝﺠﺩﺭﺍﻥ ﻤﺒﺎﺸﺭﺓ ﺩﻭﻥ ﻓﺭﺍ
. ﺨﻠﻔﻬﺎ