Prevention and fire protection requirements in the facilities (Part I) second tabah 2008 - page 184

ﺍﻝﺒﺎﺏ
ﺍﻝﺤﺎﺩﻱ ﻋﺸﺭ
١٨٦
١١-٩/٤/٣/٢
ﺇﺫﺍ ﻜﺎﻨﺕ ﺠﻭﺍﻨﺏ ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ ﻤﻔﺘﻭﺤﺔ ﺒﻨﺴﺒﺔ ﻻ ﺘﻘل ﻋﻥ
٢٥%
ﻤﻥ ﻤـﺴﺎﺤﺔ ﺍﻝﺠـﺩﺍﺭ
ﺍﻝﺨﺎﺭﺠﻲ ﻝﻠﻤﺒﻨﻰ ﻭﻋﻠﻰ ﺠﻬﺘﻴﻥ ﻤﺘﻘﺎﺒﻠﺘﻴﻥ، ﻴﻌﺘﺒﺭ ﺫﻝﻙ ﺍﻝﻤﻭﻗﻑ ﻤﻔﺘﻭﺡ ﻭﻴﻤﻜﻥ ﺍﻻﺴﺘﻐﻨﺎﺀ ﻋـﻥ
ﻨﻅﺎﻡ ﺍﻝﻤﺭﺸـﺎﺕ ﺍﻝﺘﻠﻘﺎﺌﻴﺔ ﻝﻤﻴﺎﻩ
ﺇﻁﻔﺎﺀ ﺍﻝﺤﺭﻴﻕ
.
١١-٩/٥
ﻤﻌﺩﺍﺕ ﻤﻜﺎﻓﺤﺔ ﺍﻝﺤﺭﻴﻕ ﻭﺍﻹﻨﺫﺍﺭ
:
ﻴﺠﺏ ﺘﻭﻓﻴﺭ
ﻤﺘﻁﻠﺒﺎﺕ ﺍﻝﺒﺎﺏ ﺍﻝﺭﺍﺒﻊ
"
ﺍﻝﻤﺘﻁﻠﺒﺎﺕ ﺍﻝﻌﺎﻤﺔ ﻝ
ﻠﺨﺩﻤﺎﺕ
ﺍﻝﻬﻨﺩﺴﻴﺔ
"
ﺇﻀﺎﻓﺔ ﻝﻠﺸﺭﻭﻁ ﺍﻝﻭﺍﺭﺩﺓ ﻓﻲ ﺍﻝﺠﺩﻭل
١١-٦.
١١-٩/٥/١
ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﻤﻌﺩﺍﺕ ﺍﻝﺤﺭﻴﻕ ﻭﺍﻹﻨﺫﺍﺭ ﻤﻥ ﺤﻴـﺙ ﺍﻝﺘـﺼﻤﻴﻡ ﻭﺍﻝﺘﻨﻔﻴـﺫ ﻭﺍﻝـﺼﻴﺎﻨﺔ ﻭﻓﻘـﺎﹰ
ﻝﻼﺸﺘﺭﺍﻁﺎﺕ ﺍﻝﺨﺎ
ﺼﺔ ﺒﻤﻌﺩﺍﺕ ﺍﻹﻁﻔﺎﺀ ﻭﺍﻹﻨﺫﺍﺭ ﺃﻭ ﺩﻝﻴل ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ
.
١١-٩/٥/٢
ﻻ ﻴﺠﻭﺯ ﺘﻨﻔﻴﺫ ﺃﻴﺔ ﺇﻨﺸﺎﺀﺍﺕ ﺃﻭ ﺘﺭﻜﻴﺏ ﺃﻴﺔ ﻤﻌﺩﺍﺕ ﺘﺘﻌﻠﻕ ﺒﺘﺨﺯﻴﻥ ﺃﻭ ﺘﺯﻭﻴﺩ ﺍﻝﺴﻴﺎﺭﺍﺕ ﺒﺎﻝﻭﻗﻭﺩ
ﻓﻲ ﺍﻝﻤﺒﻨﻰ، ﺇﻻ ﺒﺈﺫﻥ ﺨﺎﺹ ﻤﻥ ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﻭﺒﺸﺭﻭﻁ ﺨﺎﺼﺔ
.
١١-٩/٥/٣
ﻴﺠﻭﺯ ﻝﻠﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ، ﺃﻥ ﻴﻁﻠﺏ ﻤﻌﺩﺍﺕ ﺇﻀﺎﻓﻴﺔ ﺃﻭ ﺒ
ﺩﻴﻠﺔ ﻋﻥ ﺒﻌﺽ ﺍﻻﺤﺘﻴﺎﻁـﺎﺕ ﺍﻝﻭﻗﺎﺌﻴـﺔ
ﺍﻝﻤﻁﻠﻭﺒﺔ ﻭﻓﻘﺎﹰ ﻝﻠﺸﺭﻭﻁ
.
:٦-١١ ﺠﺩﻭل
ﻤﻌﺩﺍﺕ ﻤﻜﺎﻓﺤﺔ ﺍﻝﺤﺭﻴﻕ ﻭﻨﻅﻡ ﺍﻹﻨﺫﺍﺭ ﻓﻲ ﻤﺒﺎﻨﻲ ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ
ﺤﺴﺏ ﺍﻝﻔﺌﺔ ﻭﺍﻻﺭﺘﻔﺎﻉ ﻭﺍﻝﺘﺼﻨﻴﻑ ﺍﻹﻨﺸـﺎﺌﻲ
ﺍﻝﻨﻭﻉ
ﺍﻝﺤﺎﻻﺕ ﺍﻝﻤﻁﻠﻭﺒﺔ
١.
ﻤﻌﺩﺍﺕ ﺍﻹﻁﻔﺎﺀ ﺍﻝﻴﺩﻭﻴﺔ
:
.ﺃ
ﺎﻁﻔ
ﻴﺎﺕ ﻴﺩﻭﻴﺔ
ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ
٢.
ﺍﻝﺘﺭﻜﻴﺒﺎﺕ ﺍﻝﺜﺎﺒﺘﺔ
:
.ﺃ
ﺸﺒﻜﺔ ﺨﺭﺍﻁﻴﻡ ﻤﻁﺎﻁﻴﺔ
ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ ﻭﺍﻝﺤﺎﻻﺕ
.
.ﺏ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺠﺎﻓﺔ
ﻏﻴﺭ ﻤﻁﻠﻭﺒﺔ
.
.ﺝ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺭﻁﺒﺔ
ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ
.
.ﺩ
ﺸﺒﻜﺔ ﻓﻭﻫﺎﺕ ﺨﺎﺭﺠﻴﺔ
ﺩﺍﺨل ﺴﻭﺭ ﺍﻝﻤﺸﺎﺭﻴﻊ ﺍﻝﻜﺒﻴﺭﺓ
.
٣.
ﺍﻷﻨﻅﻤﺔ ﺍﻝﺘﻠﻘﺎﺌﻴﺔ ﺍﻝﺜﺎﺒﺘﺔ
:
.ﺃ
ﺸﺒﻜﺔ ﺘﻠﻘﺎﺌﻴﺔ ﻝﻤﺭﺸﺎﺕ ﻤﻴﺎﻩ
ﻤﻜﺎﻓﺤﺔ ﺍﻝﺤﺭﻴﻕ
ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ ﺘﺤـﺕ ﻤـﺴﺘﻭﻯ ﺍ
) ﻷﺭﺽ
ﺍﻝـﺴﺭﺩ
( ﺍﺏ
، ﻭﻤﻐﻠﻘـﺔ
ﺍﻝﺠﻭﺍﻨﺏ
.
.ﺏ
ﺸﺒﻜﺔ ﺘﻠﻘﺎﺌﻴﺔ ﻝﻤﺭﺸﺎﺕ ﻤﻭﺍﺩ
ﺃﺨﺭﻯ
ﺃﻤﺎﻜﻥ ﺍﻝﺨﻁﻭﺭﺓ ﺍﻝﺨﺎﺼﺔ ﺤﻴﺙ ﻻ ﻴﻤﻜﻥ ﺍﺴﺘﺨﺩﻡ ﺍﻝﻤﻴﺎﻩ
.
٤.
ﻤﻌﺩﺍﺕ ﺇﻨﺫﺍﺭ ﺍﻝﺤﺭﻴﻕ
:
.ﺃ
ﺸﺒﻜﺔ ﺇﻨﺫﺍﺭ ﻴﺩﻭﻱ
ﻓﻲ ﺠﻤﻴﻊ ﺍﻝﻁﻭﺍﺒﻕ ﻭﺍﻝﺤﺎﻻﺕ
.
.ﺏ
ﺸﺒﻜﺔ ﺇﻨﺫﺍﺭ ﺘﻠﻘﺎﺌﻲ
ﻓﻲ ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ ﻤﻐﻠﻘﺔ ﺍﻝﺠﻭﺍﻨﺏ
.