Prevention and fire protection requirements in the facilities (Part I) second tabah 2008 - page 183

ﺍﻝﺒﺎﺏ
ﺍﻝﺤﺎﺩﻱ ﻋﺸﺭ
١٨٥
١١-٩
ﺸـﺭﻭﻁ ﻭﻗﺎﺌﻴﺔ ﺨﺎﺼـﺔ
"
ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ
"
١١-٩/١
ﻤﺒﺎﻨﻲ ﻤﺴﺘﻭﺩﻋﺎﺕ
"
" ﻤﻭﺍﻗﻑ
ﺍﻝﺴﻴﺎﺭﺍﺕ
:
ﻤﺒﺎﻨﻲ ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ
:
ﻫﻲ ﺍﻝﻤﺒﺎﻨﻲ ﺍﻝﻤﺴﺘﻌﻤﻠﺔ ﻓﻲ ﺘﺨﺯﻴﻥ ﻭﻭﻗﻭﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ ﺒﺸﻜل ﻤـﺴﺘﻤﺭ ﺃﻭ
ﻤﺅﻗﺕ، ﻭﺘﻌﺘﺒﺭ ﻓﻲ ﻫﺫﺍ
ﺍﻝﻤﻔﻬﻭﻡ ﺘﺎﺒﻌﺔ ﻝﻤﺒ
ﺎﻨﻲ ﺍﻝﻤﺴﺘﻭﺩﻋﺎﺕ
،
ﻝﺫﺍ ﺘﻁﺒﻕ ﺍﻝﺸﺭﻭﻁ ﺍﻝﻭﻗﺎﺌﻴﺔ ﻝﻠﺤﻤﺎﻴﺔ ﻤﻥ
ﺍﻝﺤﺭﻴﻕ ﻓﻲ ﻤﺒﺎﻨﻲ ﺍﻝﻤﺴﺘﻭﺩﻋﺎﺕ ﺒﺸﻜل ﻋﺎﻡ ﻋﻠﻰ ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ ﺇﻀﺎﻓﺔ ﻝﻬﺫﻩ ﺍﻝﺸﺭﻭﻁ
ﺍﻝﺨﺎﺼﺔ
.
ﺘﻨﻘﺴـﻡ ﻤﺒﺎﻨﻲ ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ ﻤﻥ ﺍﻝﻨﺎﺤﻴﺔ ﺍﻝﻤﻌﻤﺎﺭﻴﺔ ﺇﻝﻰ ﻓﺌﺎﺕ ﻜﺎﻝﺘﺎﻝﻲ
:
١١-٩/١/١
ﺍﻝﻔﺌـﺔ
( ﺃ )
ﻤﺒﺎﻨﻲ ﻤﻔﺘﻭﺤﺔ ﺍﻝﺠﻭﺍﻨﺏ ﺘﻘﺎﺩ
ﻓﻴﻬﺎ ﺍﻝﺴﻴﺎﺭﺓ ﻝﻤﻜﺎﻥ ﻭﻗﻭﻓﻬﺎ ﻭﻋﻨﺩ ﺍﻝﺨﺭﻭﺝ
.
١١-٩/١/٢
ﺍﻝﻔﺌـﺔ
(ﺏ)
ﻤﺒﺎﻨﻲ ﻤﻐﻠﻘﺔ ﺍﻝﺠﻭﺍﻨﺏ ﺘﻘﺎﺩ ﻓﻴﻬﺎ ﺍ
ﻝﺴﻴﺎﺭﺓ ﻝﻤﻜﺎﻥ ﻭﻗﻭﻓﻬﺎ ﻭﻋﻨﺩ ﺍﻝﺨﺭﻭﺝ
.
١١-٩/١/٣
ﺍﻝﻔﺌـﺔ
(ﺝ)
ﻤﺒﺎﻨﻲ ﻴﻤﻜﻥ ﺇﺩﺨﺎل ﺍﻝﺴﻴﺎﺭﺓ
ﻝﻤﻜﺎﻥ ﻭﻗﻭﻓﻬﺎ ﻭﺇﺨﺭﺍﺠﻬﺎ ﺒﺸـﻜل ﺁﻝﻲ
.
١١-٩/٢
ﺨﻁﻭﺭﺓ ﺍﻝﺤﺭﻴﻕ
:
ﺘﺼﻨﻑ ﺨﻁﻭﺭﺓ ﺍﻝﺤﺭﻴﻕ ﻓﻲ ﻤﺒﺎﻨ
ﻲ ﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ ﺒﺎﻋﺘﺒﺎﺭﻫﺎ ﺨﻁﻭﺭﺓ
ﻤﺘﻭﺴﻁﺔ
ﻜﻤﺎ ﺒﻴﻥ ﻓﻲ ﺍﻝﺠﺩﻭل
ﺒﺎﺏﺍﻝ ﻓﻲ١-١
ﺍﻷﻭل
"
ﺍﻝﻤﺘﻁﻠﺒﺎﺕ ﺍﻝﻭﻗﺎﺌﻴﺔ ﺍﻝﻌﺎﻤﺔ ﻝﻠﻤﺒﺎﻨﻲ
."
١١-٩/٣
ﺍﻝﻤﺘﻁﻠﺒﺎﺕ ﺍﻹﻨﺸﺎﺌﻴﺔ
:
ﻴﺠﺏ ﺘﻁﺒﻴﻕ ﺸﺭﻭﻁ ﺍﻝﺒﺎﺏ ﺍﻷﻭل ﻝﺘﻭﻓﻴﺭ ﺴﻼﻤﺔ ﺍﻝﻬﻴﻜل ﺍﻹﻨﺸﺎﺌﻲ ﻤﻥ ﺃﺨﻁﺎﺭ ﺍﻝﺤﺭﻴﻕ، ﻭﻤﺎ ﺠﺎﺀ ﻓﻲ
ﺍﻝﻤﺘﻁﻠﺒﺎﺕ ﺍﻹﻨﺸﺎﺌﻴﺔ ﻝﻬﺫﺍ ﺍﻝ
. ﺒﺎﺏ
١١-٩/٤
ﺍﻝﺴﻴﻁﺭﺓ ﻋﻠﻰ ﺍﻨﺘﺸﺎﺭ ﺍﻝﺤﺭﻴﻕ
١١-٩/٤/١
ﺍﻝﻤﻨﺤﺩﺭﺍﺕ ﻝﻤﻭﺍﻗﻑ ﺍﻝﺴﻴﺎﺭﺍﺕ ﺘﺤﺕ ﻤﺴﺘﻭﻯ ﺍﻷﺭﺽ
:
١١-٩/٤/١/١
ﻻ ﺘﻌﺘﺒﺭ ﻤﻨﺤﺩﺭﺍﺕ
ﺩﺨﻭل ﻭﺨﺭﻭﺝ ﺍﻝﺴﻴﺎﺭﺍﺕ
ﺴـﺒﻼﹰ ﻝﻠﻬﺭﻭﺏ، ﺇﻻ ﺇﺫﺍ ﺨﺼﺹ ﺠﺯﺀ ﻤﻨﻬـﺎ
ﻝﺫﻝﻙ ﻤﺤﻤﻲ ﺒﺤﺎﺠﺯ ﻭﺍﻗﻲ، ﻭﺘﺘﻭﺍﻓﺭ ﻓﻴﻪ ﺍﻝﺸﺭﻭﻁ ﺍﻝﻌﺎﻤﺔ ﻝﺴﺒل ﺍﻝﻬﺭﻭﺏ
.
١١-٩/٤/١/٢
ﻴﺠﺏ
ﺃﻥ ﻻ ﺘﺯﻴﺩ ﻨﺴﺒﺔ ﺍﻝﻤﻨﺤﺩﺭ ﻤﻥ ﻭ ﺇﻝﻰ ﺍﻝﺴﺭﺩﺍﺏ ﻋﻥ
) ١٠:١ (
ﻜﻤـﺎ ﻴﺠـﺏ ﺃﻥ ﻴﺘـﻭﻓﺭ
ﻤﻨﺤﺩﺭﺍﻥ ﻤﺘﺒﺎﻋﺩﺍﻥ ﻋﻠﻰ ﺍﻷﻗل، ﻭﻴﻔﻀل
ﺃﻥ ﻴﻜﻭﻨﺎ
ﻋﻠﻰ ﺠﻬﺘﻴﻥ ﻤﺘﻘﺎﺒﻠﺘﻴﻥ، ﻭﻓﻲ ﺤﺎﻝﺔ ﺘﻌـﺫﺭ
ﺫﻝﻙ ﻴﻘﺭﺭ ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﻤﺎ ﻴﺭﺍﻩ ﻤﻨﺎﺴﺒﺎﹰ ﺤﺴﺏ
ﺍﻝﺤﺎﻝﺔ
.
١١-٩/٤/٢
ﺍﻷﺭﻀﻴﺔ
:
١١-٩/٤/٢/١
ﻴﺠﺏ ﻋﻤل ﻤﻴﻭل ﻓﻲ ﺃﺭﻀﻴﺔ ﺍﻝﺴﺭﺩ
ﺍﺏ ﺘﺅﺩﻱ ﺇﻝﻰ ﻗﻨﻭﺍﺕ ﻝﺘﺠﻤﻴﻊ ﺍﻝﻤﻴﺎﻩ ﺃﻭ ﺍﻝﺯﻴﻭﺕ ﺍﻝﻤﻨﺴﻜﺒﺔ
ﻭﺘﺼﺭﻴﻔﻬﺎ ﻋﺒﺭ ﻓﺘﺤﺎﺕ ﺘﺼﺭﻴﻑ ﺃﺭﻀﻴﺔ، ﺜﻡ ﺇﻝﻰ ﻓﺎﺼل ﺯﻴﻭﺕ ﻭﻤﻨﻪ ﺇﻝﻰ ﺍﻝﻤﺠﺎﺭ
ﻱ ﺍﻝﻌﺎﻤﺔ،
ﻭﻓﻘﺎﹰ ﻝﻸﺼﻭل ﺍﻝﻬﻨﺩﺴﻴﺔ
.
١١-٩/٤/٣
ﺍﻝﺠﺩﺍﺭ ﺍﻝﺠﺎﻨﺒﻲ
:
١١-٩/٤/٣/١
ﺘﻐﻁﻰ ﺍﻝﻨﻭﺍﻓﺫ ﺍﻝﺠﺎﻨﺒﻴﺔ ﺍﻝﻤﻁﻠﺔ ﻋﻠﻰ ﺍﻝﺸﺎﺭﻉ ﺍﻝﻌﺎﻡ ﺒﺎﻝﺯﺠﺎﺝ ﺍﻝﻤﺴﻠﺢ، ﺃﻭ ﺍﻝﺴﻠ
ﻙ ﺍﻝﺸﺒﻜﻲ ﺍﻝﺴﻤﻴﻙ
ﻝﻤﻨﻊ ﺩﺨﻭل ﺃ
ﻋﻘﺎﺏ ﺍﻝﺴﺠﺎﺌﺭ ﻭﺍﻝﻤﻬﻤﻼﺕ ﻭﻏﻴﺭﻫﺎ
.