Prevention and fire protection requirements in the facilities (Part I) second tabah 2008 - page 95

ﺍﻝﺒﺎﺏ ﺍﻝﺭﺍﺒﻊ
٩٧
ﺍﻝﺒﺎ
ﺏ ﺍﻝﺭﺍﺒﻊ
ﺍﻝﻤﺘﻁﻠﺒﺎﺕ ﺍﻝﻌﺎﻤﺔ ﻝﻠﺨﺩﻤﺎﺕ ﺍﻝﻬﻨﺩﺴﻴﺔ
ﺘﺼﻤﻡ ﻭﺘﻨﻔﺫ ﺍﻝﺨﺩﻤﺎﺕ ﺍﻝﻬﻨﺩﺴﻴﺔ ﻓﻲ ﺍﻝﻤﺒﺎﻨﻲ ﻝﺤﻤﺎﻴﺘﻬﺎ ﻤﻥ ﺍﻝﺤﺭﻴﻕ ﻭﻓﻘﺎ ﻝﺸﺭﻭﻁ ﻫﺫﺍ ﺍﻝﺒﺎﺏ
.
٤-١
ﺍﻝﺘﻬﻭﻴ
ﻭﺍﻝﺘﻜﻴﻴﻑ ﺍﻝﻤﺭﻜﺯﻱ
:
٤-١/١
ﻴﺘﻀﻤﻥ ﺘﺼﻤﻴﻡ ﺠﻬﺎﺯ ﺍﻝﺘﻜﻴﻴﻑ ﺍﻝﻤﺭﻜﺯﻱ ﺍﻻﺤﺘﻴﺎﻁﺎﺕ ﺍﻝﻜﺎﻓﻴﺔ ﻝﻤﻨﻊ ﺍﻨﺘﺸﺎﺭ ﺍﻝﺤﺭﻴﻕ ﻭﺍﻝﺩﺨﺎﻥ
ﺨﻼ
ل ﻗﻨﻭﺍﺕ ﺍ
ﻝﺘﻜﻴﻴﻑ ﻭﻓﻕ ﻫﺫﻩ ﺍﻝﺸﺭﻭﻁ
.
٤-١/٢
ﻴﺭﺍﻋﻰ ﻋﻨﺩ ﺍﺨﺘﻴﺎﺭ ﻤﻭ
ﺂ ﻗﻊ ﻤ
ﺨﺫ ﺍﻝﻬﻭﺍﺀ ﺍﻝﺨﺎﺭﺠﻴﺔ ﺍﻝﺨﺎﺼﺔ ﺒﺠﻬﺎﺯ ﺍﻝﺘﻜﻴﻴﻑ ﻋﺩﻡ ﺘﺠﺎﻭ
ﻩ ﻤـﻊ ﺭ
ﺃﻤﻜﻨﺔ ﺃﻭ ﻤﺼﺎﺩﺭ ﺘﻜﻭﻥ ﻋﺭﻀﺔ ﻝﻤﺨﺎﻁﺭ ﻨﺸﻭﺏ ﺤﺭﻴﻕ
.
٤-١/٣
ﻴﻔﻀل ﺃﻥ ﺘﻭﺯﻉ ﻗﻨﻭﺍﺕ ﺍﻝﺘﻜﻴﻴﻑ ﺘﻭﺯﻴﻌﺎ ﻻ ﻤﺭﻜﺯﻴﺎ
،
ﻭﺫﻝﻙ ﺒﺄﻥ ﺘﻘﺴﻡ ﺇﻝـﻰ ﺃﻗـﺴﺎﻡ ﻤـﺴﺘﻘﻠﺔ
ﻴﺨﺘﺹ ﻜل ﻤﻨﻬﺎ ﺒﺠﺯﺀ ﻤ
، ﻥ ﺍﻝﻤﺒﻨﻰ
ﺃﻤﺎ ﺍﻷﻤﺎﻜﻥ ﺍﻝﻤﻌﺭﻀﺔ ﻝﺨﻁﻭﺭﺓ ﻨﺸﻭﺏ ﺤﺭﻴﻕ ﻜﺎﻝﻤﻁﺎﺒﺦ
ﻭﺍﻝﺤﻤﺎﻤﺎﺕ ﻭﻏﻴﺭﻫﺎ ﻓﻴﺠﺏ ﺘﻭﻓﻴﺭ ﺃﺠﻬﺯﺓ ﺘﻜﻴﻴﻑ ﻤﻨﻔﺼﻠﺔ ﻝﻬﺎ
.
٤-١/٤
ﻴﺠﻭﺯ ﻝﻠﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﺃﻥ ﻴﻁﻠﺏ ﻓﻲ ﺤﺎﻻﺕ ﺨﺎﺼﺔ ﺘﺭﻜﻴﺏ ﻤﻔﺘﺎﺡ ﻁﻭﺍﺭﺉ ﻋﻠﻰ ﺠﻬﺎﺯ ﺍﻝﺘﻜﻴﻴﻑ
ﻓﻲ ﻤﻜﺎﻥ ﻤﻨﺎﺴﺏ ﻝﺨﺩﻤﺔ ﺭﺠﺎل ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ
.
٤-١/٥
ﻴﺸﺘﺭﻁ ﻓﻲ ﺍﻝﻤﺒﺎﻨﻲ
ﺫﺍﺕ ﺍﻝﻭﺍﺠﻬﺎﺕ ﺍﻝﻤﻐﻠﻘﺔ ﻷﺴﺒﺎﺏ ﺘﺘﻌﻠﻕ ﺒﺘﺼﻤﻴﻡ ﺠﻬﺎﺯ ﺍﻝﺘﻜﻴﻴﻑ ﻭﺠﻭﺩ ﻨﻭﺍﻓﺫ
ﺃﻭ ﻓﺘﺤﺎﺕ ﺨﺎﺼﺔ ﻓﻲ ﻫﺫﻩ ﺍﻝﻭﺍﺠﻬﺎﺕ ﻝﻴﺘﻤﻜﻥ ﺭﺠﺎل ﺍﻝﺩﻓﺎﻉ ﺍﻝﻤﺩﻨﻲ ﻤﻥ ﺘﺼﺭﻴﻑ ﺍﻝﺩﺨﺎﻥ ﻓـﻲ
ﺍﻝﻤﺒﻨﻰ ﻋﻨﺩ ﻨﺸﻭﺏ ﺤﺭﻴﻕ
.
٤-١/٦
ﻌﺘﺒﺭ ﺘ
ﺍﻝﻘﻨﻭﺍﺕ ﺍﻝﺭﺌﻴﺴﻴﺔ ﻝﺠﻬﺎﺯ ﺍﻝﺘﻜﻴﻴﻑ ﺨﻼل ﻤﻤﺭﺍﺕ ﺭﺃﺴﻴﺔ ﺃﻭ ﺃﻓﻘﻴﺔ ﻤﻨﺸﺄﺓ ﻤﻥ ﻤﻭﺍﺩ ﻏﻴـﺭ
ﻗﺎﺒﻠ
ﺔ ﻝﻼﺤﺘﺭﺍﻕ ﻜﻭﺤﺩﺓ ﻤﺎﻨﻌﺔ ﻝﻠﺤﺭﻴﻕ
،
ﻤﻊ ﻭﺠﻭﺩ ﻓﺘﺤﺎﺕ ﻤﻨﺎﺴﺒﺔ ﺫﺍﺕ ﺃﺒﻭﺍﺏ ﻤﺎﻨﻌﺔ ﻝﻠﺤﺭﻴـﻕ
ﻝﺘﺴﻬﻴل ﺇﺠﺭﺍﺀﺍﺕ ﺍﻝﺼﻴﺎﻨﺔ
.
٤-١/٧
ﻋﻨﺩ ﺍﺨﺘﺭﺍﻕ ﻗﻨﻭﺍﺕ ﺍﻝﺘﻜﻴﻴﻑ ﻝﻠﺠﺩﺭﺍﻥ ﺃﻭ ﺍﻷﺴﻘﻑ ﺍﻝﻤﺎﻨﻌﺔ ﻝﻠﺤﺭﻴﻕ ﻓﻲ ﺍﻝﺒﻨﺎﺀ ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ
ﻤﻘﺎﻭﻤﺘﻬﺎ ﻝﻠﺤﺭﻴﻕ
ﺒﻘﺩﺭ
ﺩﺭﺠﺔ ﻤﻘﺎﻭﻤﺔ
ﻝﺠﺩﺭﺍﻥ
،
ﻭﺘﻐﻠﻕ ﺘﻠﻘﺎﺌﻴﺎ ﺒﻔﻌل ﻭﺼﻠﺔ ﻤﻨﺼ
ﻬﺭﺓ ﺘﻌﻤـل
ﻋﻨﺩ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺘﺘﺭﺍﻭﺡ ﺒﻴﻥ
(٤٨ـ٨٦)
ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ
.
٤-١/٨
ﺘﺠﻬﺯ ﻗﻨﻭﺍﺕ ﻨﻅﺎﻡ ﺍﻝﺘﻬﻭﻴﺔ ﻭﺍﻝﺘﻜﻴﻴﻑ ﺍﻝﻤﺭﻜﺯﻱ ﺒﻜﺎﺸﻔﺎﺕ ﻝﻠﺩﺨﺎﻥ ﺘﻌﻤل ﺘﻠﻘﺎﺌﻴﺎ ﻋﻠـﻰ ﺇﻴﻘـﺎﻑ
ﺘﺸﻐﻴل ﺍﻝﺠﻬﺎﺯ
ﺒﻜﺎﻤﻠﺔ
ﻋﻨﺩ ﺍﻜﺘﺸﺎﻑ ﺍﻝﺩﺨﺎﻥ ﻭﺘﺩﻴﺭ ﻓﻲ ﺍﻝﻭﻗﺕ ﻨﻔﺴﻪ ﻤﺭﺍﻭﺡ ﺸـﺎﻓﻁﺔ ﻝﻁـﺭﺩ
ﺍﻝﺩﺨﺎﻥ ﻤﻥ
ﺍﻝﻤﺒﻨﻰ
.
٤-١/٩
ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ
ﺍﻝﻤﻭﺍﺩ ﺍﻝﻌﺎﺯﻝﺔ ﺍﻝﻤﺴﺘﻌﻤﻠﺔ ﻓﻲ ﺘﻐﻠﻴﻑ ﻗﻨﻭﺍﺕ ﺍﻝﻬﻭﺍﺀ ﺒﺎﻝﺩﺍﺨل ﻭﺍﻝﺨﺎﺭﺝ ﻏﻴـﺭ
ﻗﺎﺒﻠﺔ ﻝﻼﺤﺘﺭﺍﻕ ﻭﺃﻥ ﻻ ﻴﻘل ﺴﻤﻜﻬﺎ ﻤﻥ
( ﺴـﻡ ٣)
ﻭﻻ ﻴﺠﻭﺯ ﺍﺴﺘ
ﻌﻤﺎل ﻤﺎﺩﺓ ﻗﺎﺒﻠﺔ ﻝﻼﺤﺘـﺭﺍﻕ
. ﻓﻴﻬﺎ